Engineer Library

F-Gas Leak Test Frequency Calculator

F-Gas Leak Test Calculator
To determine the maximim time between leak tests, select the refrigerant and enter the charge in kg.

There’s no maximum period of time between leak checks on:

  • hermetically sealed refrigeration and air conditioning systems unless they contain F gas equivalent to 10 tonnes of carbon dioxide (that’s equal to 2.6kg of HFC404A or 7kg of HFC 134a)
  • refrigeration systems in vehicles, except refrigerated trucks or trailers


If you install a system to automatically detect leaks, you can double the period of time allowed between leak checks. For example, with a leak detection system you must check a product that contains F gas equivalent to 5 tonnes of carbon dioxide every 2 years.


When to fit automatic leak detection

You must fit a leak detection system if your equipment contains F gas equivalent to 500 tonnes or more of carbon dioxide. This does not apply to electrical switchgear or organic Rankine cycles installed before 1 January 2017.


The leak detection system must alert you, or a service company responsible for your equipment, if it detects a leak.


You must have your leak detection system checked:

  • every 6 years on electrical switchgear
  • every year on all other equipment containing F gas


Updated 22/08/25 source: https://www.gov.uk/guidance/checking-f-gas-equipment-for-leaks